nothing but datacenters facility nbd-01

NBD-OM-001 · section 2

Envelope

The building: its walls, its perimeter, its doors, and what to do if someone is inside it.

Revision 0 (draft01) · published 2026-09-29 04:03-07:00 · source ff3c1ff

2.1 Building description

The building is a sealed volume. Its walls are insulated panels without windows. Its roof carries plant and nothing else. It has no front, because nothing approaches it from any particular side.

The building has been recorded from several positions, reproduced below as reference drawings. None of those positions is occupied. The drawings differ in the direction of view. Where a drawing names a setting, the setting is left out; the building does not change with it.

Figure 2.1. The building. Windowless on every face; the halls are the long roofs.
Figure 2.1 The building. Windowless on every face; the halls are the long roofs. · drawing ref. NBD-DWG-TOWER
ElementSpecification
WallsInsulated metal panel, no openings above ground level
RoofMembrane on deck; plant platforms; no access hatch in normal use
WindowsNone
SignageDesignation only, at the gate (see 1.7)
ColourSelected to be unremarkable

2.2 Setting

The building does not respond to its setting. Where the ground is farmland, it stands in farmland; where the ground is coast, it stands at the coast. It is the same building in both.

Figure 2.2. The building, reference drawing for a coastal site. The coast is not drawn; the building does not change with it.
Figure 2.2 The building, reference drawing for a coastal site. The coast is not drawn; the building does not change with it. · drawing ref. NBD-DWG-COAST
Figure 2.3. The building, reference drawing for a farmland site. The fields are not drawn; the building does not change with them.
Figure 2.3 The building, reference drawing for a farmland site. The fields are not drawn; the building does not change with them. · drawing ref. NBD-DWG-FIELDS

2.3 Perimeter

The site is enclosed by a fence of the standard height for a facility of this class. It is monitored by cameras at regular intervals along its length. The cameras record continuously. The recordings are reviewed by the facility, which finds nothing, and are retained for the statutory period, after which they are deleted without having been watched by anyone.

note

The perimeter does not keep people out so much as record that they are not there.

2.4 Entry

The building has personnel doors because building codes require them. Each opens into a security vestibule: a small room with two doors, only one of which may be open at a time. A person entering is held between them while their credentials are checked.

No credentials have been issued.

Figure 2.4. Security vestibule, cutaway. Two doors; only one opens at a time.
Figure 2.4 Security vestibule, cutaway. Two doors; only one opens at a time. · drawing ref. NBD-DWG-VESTIBULE
Figure 2.5. Credential station within the vestibule.
Figure 2.5 Credential station within the vestibule. · drawing ref. NBD-DWG-VESTIBULE2

Procedure 2.4-1, Entry to the building:

  1. Present credentials at the outer door.
  2. Enter the vestibule. Wait for the outer door to close behind you.
  3. Present credentials at the inner door.
  4. The inner door does not open. No credentials are valid. Return by the outer door.
performed byverified bydatesignature

Sign-off fields are provided for regulatory form. No entry is expected.

Figure 2.6. Door to the service corridor beyond the vestibule. In operation the corridor is dark.
Figure 2.6 Door to the service corridor beyond the vestibule. In operation the corridor is dark. · drawing ref. NBD-DWG-CORRIDOR

2.5 In the event of human presence

The facility is designed on the assumption that no person will enter it. This section describes what happens if one does.

warning

The halls contain moving robotic equipment, energised conductors, inert-gas fire suppression that displaces breathable air, and temperatures and noise above comfortable limits. None of these is designed around a person.

Procedure 2.5-1, Human presence detected:

  1. The facility registers the presence at the first camera or door that observes it.
  2. Robotic equipment in the affected area stops and holds position.
  3. Fire suppression in the affected area is inhibited while presence persists.
  4. Lighting in the affected area is switched on. Apart from testing (Section 3.7), this is the only circumstance in which the lights are used.
  5. The facility records the event. It does not raise an alarm, because there is no one to receive one.
  6. When the person leaves, the lights are switched off, the equipment resumes, and the event is closed.

Presence is the most common form of intervention, and the simplest; the others are described in Section 4.9.

If you are the person: leave the way you came. Nothing here requires you, and nothing here will stop you from going.

performed byverified bydatesignature

Sign-off fields are provided for regulatory form. No entry is expected.